Humidity + Temperature Transmitters: BM-RHT-2AS

Application Areas -Building Environmental Control Systems -Commercial Construction/Retrofitting -Hospitals and Medical Centers -Walk-in Freezers, Supermarkets -Greenhouses, Food Storage, Incubators, Swimming Pools¡
DESCRIPTION: (Humidity transmitter with temperature transmitter) The BM-RHT-2AS transmitter is specifically designed for use in applications where both a temperature and humidity signal are required. The BM-RHT-2AS Wall Mount comes standard in the Designer Space enclosure designed for ease of installation and is available as a 12~35 VDC loop powered device with both temperature and humidity signal outputs.
SPECIFICATION: (Humidity Transmitter) System Accuracy: ¡À3%RH(@25¡ãC, 15%~90%RH;(¡À3~5%RH in other range) Compensated Temp.: -20¡ãC to 60¡ãC Sensor Construction: Capacitive humidity sensor HS11 Repeatability: ¡À0.5% RH Hysteresis: ¡À1% of span max Linearity: ¡À0.5% RH typical Response Time: 6 seconds @ 25¡ãC Stability: ¡À2% RH typical at 50% RH in 5 yrs. Output Signal Types: 4~20mA, 0~5 VDC(Jumper selectable), and RS485 Note: all output signals are scaled 0-100%RH Power Supply: 12 ~ 35 VDC at unit (Loop Powered) Wiring Connections: Screw Terminals (14 to 22 AWG)
SPECIFICATION: (Temperature Transmitter) Accuracy: ¡À 0.5¡ãC Supply Voltage: 12 ~ 35 VDC at unit (Loop Powered) Output: 4-20mA, 0-5VDC (Jumper selectable), ans RS485 Operating temp: -20 ~ 60¡ãC (OSA operating temp: -20 ~ 80¡ãC) Temperature sensor: NTC
Installation
_ Install in stable environments, avoiding direct light, keeping away from equipments as window, conditioner, heating and so on, avoiding directly facing to windows and doors. _ Installation height is people¡¯s sitting height or the height of equipments which mainly have demands for environmental conditions Outline dimension and installation diagram
Main Box Size: 90¡Á90¡Á30mm
Probe Size: 20x140mm(the longer probe can be selected, such as 220mm, 300mm)
|